MFP14 Three Pump Combination Device

Rated displacement

MFP14 three-pump combination

DN80-18000Kg/h

The rated displacement is 8 bar power pressure and 4 meters head. For specific displacement, see MFP14-DN80*50 pump displacement x3.

Get A Quote
Product Description
Restrictions (three-pump combination) • Pump design condition: PN16
• Pump diameter: DN80*DN50
• The water tank is an open container and cannot bear pressure.
• Maximum dynamic pressure: steam, air or other gas 13.8bar
• Standard pump working fluid specific gravity: 0.8-1.0
• Displacement per pump cycle: 19.3L (average)/single pump

 

MFT14-DN80*DN50 three-pump combination configuration table

Parts Name Part number Specification quantity
Automatic pump MET14 DN80*DN50 3
Check valve (pump inlet) H71H DN80 3
Check valve (pump outlet) DN50 3
Steam Trap FTGS14 DN15 1
Filter (Pump Inlet) YG45H DN80 3
Filter (power steam inlet) YG45H DN40 1
Ball valve (trap outlet) Q11H DN15 1
Ball valve (exhaust gas) Q11H DN25 3
Bellows stop valve WJ41H DN80 3
Exhaust/gas hose / 3
Open water collection tank / 1

 

Note: The overflow and drain ports must be connected to a safe location

 

Device connection port • Condensate inlet: 2*DN80, 2*DN150
• Exhaust port (to atmosphere): DN200
• Condensate outlet: 3*DN50
• Power medium inlet: DN40
• Overflow port: DN100
• Connection port: DN40

 

Single pump assembly dimensions/weight (approximate) mm and Kg

Pump diameter A B C D AND F G H I J  

 

N THE P
DN50*80 1820 2300 1600 1130 2180 430 350 400 400 350 195 500 1900 1500 550
Q R S T IN IN AA BB CC DD EE FF GG HH JJ
600 80 550 250 1670 280 DN100 DN150 DN300 DN150 DN100 DN40 DN50 DN40 DN100