Rated displacement
MFP14 dual pump combination device
DN80-1200Kg/h
The rated displacement is 8 bar power pressure and 4 meters head. For specific displacement, see MFP14-DN80*50 pump displacement x2.
| Restrictions (two-pump combination) | • Pump design condition: PN16 • Pump diameter: DN80*DN50 • The water tank is an open container and cannot bear pressure. • Maximum dynamic pressure: steam, air or other gas 13.8bar • Standard pump working fluid specific gravity: 0.8-1.0 • Displacement per pump cycle: 19.3L (average)/single pump |
MFT14-DN80*DN50 double pump combination configuration table
| Parts Name | Part number | Specification | quantity |
| Automatic pump | MET14 | DN80*DN50 | 2 |
| Check valve (pump inlet) | H71H | DN80 | 2 |
| Check valve (pump outlet) | DN50 | 2 | |
| Steam Trap | FTGS14 | DN15 | 1 |
| Filter (power steam inlet) | GL11H | DN25 | 1 |
| Ball valve (trap outlet) | Q11H | DN15 | 1 |
| Ball valve (exhaust gas) | Q11H | DN25 | 2 |
| Wafer Butterfly Valve | D71 | DN80 | 2 |
| Exhaust/gas hose | / | 2 | |
| Open water collection tank | / | 1 | |
Note: The overflow and drain ports must be connected to a safe location
| Device connection port | • Condensate inlet: 2*DN80 • Exhaust port (to atmosphere): DN200 • Condensate outlet: DN50 • Power medium inlet: 1″ • Overflow port: DN80 • Water tank drain port: 2″ |
Single pump assembly dimensions/weight (approximate) mm and Kg
| Pump diameter | A | B | C | D | AND | F | G | H | I | J | K |
| DN50*80 | 1820 | 1070 | 1160 | 1220 | 1670 | 1100 | 1060 | 200 | 250 | 450 | 200 |
| L | N | THE | AA | BB | CC | DD | EE | FF | GG | HH | |
| 1170 | 170 | 520 | DN80 | DN80 | DN200 | DN80 | 3″ | 2″ | DN50 | 1″ |